EN6000B7 Series Given Controller

    The EN6000B7 series instrument is a specified value control apparatus. It can directly control the output to a controlled object in order to carry out a predictable action. The instrument has many control modes including the Auto/Manual, maintain, jump step, etc.
 
Function Characteristics

  Flexible control mode: An EN6000B7 series apparatus uses a multi-protection method and isolated design technology with a powerful anti-interference ability and high reliability. The control signal of 0-10mA, 4-20mA or 0-20mA can be set through software. The accuracy is within ±0.2%FS.

  Instrument display: An OLED screen is used that has high brightness, high resolution and wide angle of vision. It displays hint messages, setup parameters, control messages, engineering units, alarm states, etc.

  Standard casing size: There are three panel sizes (160mm×80mm, 80mm×160mm, 96mm×96mm) available so an instrument with similar simple functions can be substituted.

  Communication function: A RS485 communication interface is available (as an option) to form a computer monitoring system based on multiple instruments and a PC that has the bus characteristics defined by the ENVADA communication protocol (supported by many host computer configuration software) or MODBUS protocol allowing the functional operation of a instrument to be carried out on a host computer seemlessly. The user can choose a communication rate among 2400, 4800, 9600, 19200bps. The standard communication software operated in a PC is available.

  Advanced parameter protection function: A parameter protection function can be set to avoid any illegal operation.



Main Technological Specification

Item

Descriptions

Output signal

Control output

Signal type

4-20mA or 0-20mA (optional): Max load: 500Ω

0-10mA: Max load: 1000Ω

Set through software

Accuracy

±0.2%

Control curve

At most 8 curves, each curve has 32 segments at most,each segment time is from 1s to 10 hours

State output

Time signal

Relay contact: 250VAC/1A or 30VDC/1A resistance load

SSR driver voltage Von: 13±2VDC/Max current: 30mA, Voff: 2VDC

Program state

Program end

Display mode

Screen: 128×64 dot matrix OLED screen

Output state display and operation state display

Communication

RS232: One instrument; RS485: 255 instruments at most

Address: 0-99

Baud rate: 2400, 4800, 9600, 19200 bps (set by user)

Protection mode

Auto restoration from an abnormal working state. The setup parameters and history data are automatically stored and will not be lost in power-off. Fault code directive, multiple alarm modes and multi-level parameter protection are available

Power supply

100-240VAC (-15%-+10%) 50/60Hz or 24VDC (-15%-+25%)

Power consumption

<5W

Working condition

Environment temperature: 0-50℃

Environment humidity: 5-85%RH (below the dew point)

Continual vibration: Amplitude in X, Y and Z<1mm, Frequency<50Hz

Transport and storage

Temperature: -25-75℃

Humidity: 5-95%RH (below the dew point)



Classification