EN1000D Series Signal Isolator/Isolating Safety Gate

   An EN1000D series isolating safety gate is an excellent relative device used in the connection between the instrument in a control room and the instrument in a working place, and is widely applied to the industry procedure control system and especially the place where the nature safety system of safety and explosion-proof is required.


   EN1000D signal isolator is the most valid device to build up the anti-interference ability of system in the design of an industry control system.

 
Function Characteristics

  Electromagnetism isolation among power supply, input loop and output loop.

  Complete modularization design, small volume and low power consumption.

  The stable time is 3-5s in power-on.

  The calibrations of zero and FS are not required.·

  Thin card construction, inflammable shell (thickness: 16mm), suited for assemble installation and configuration, easy for dismounting.

  Pull-in wiring terminal, independent power supply wiring terminal, reliable power-on pull-in, convenient and easy for installation, wiring and maintenance.


Main technological specification

Isolation intensity

1500-2500VAC/1 min 50Hz among I/O/power supply/meter shell (as well as wiring terminal) 

Power Supply

Independent power supply wiring terminal. Power supply: 20-35VDC

Wiring terminal

There are 14 sockets of pull-in wiring terminal of 3mm available. The socket labels of wiring terminal are as follows:
Input wiring terminal: 1, 2, 3, 4, 5 and 6.
Output wiring terminal: 7, 8, 9, 10, 11 and 12.
Power supply wiring terminal: 13£­, 14£«.
Multi-conductor or single conductor cable (crossover area: ¡Ü2.5 square mm)

Working Temprature

0¡«+60¡æ

Storage Temprature

-20¡«+80¡æ

Relative Humidity

5¡«95%

External Dimension

Width¡ÁHeight¡ÁDepth£½16¡Á116¡Á110£¨mm£©

Weight

110g¡«120g

Installation Mode

DIN 35mm guide track. The vertical installation form is recommended



Classification/Order Guide